
MONITORING
AIR QUALITY WITH INSTRUMENTS
North Carolina State
University
Biological and Agricultural
Engineering
Raleigh, NC 27606
Tel: (919) 515-6753
email: robert_bottcher@ncsu.edu
Department of Livestock and
Poultry
Clinton, NC 28329-0318
Tel: (910) 592-8081 Fax: (910) 592-8048
email: smatthis@sampson.cc.nc.us
·
Equipment
Humidity/Temperature Pen, Humidity/Temperature Data Logger and Software
|
Adequate: |
Less than 60% |
|
Caution: |
60% to 70% |
|
Dangerous: |
More than 70% |
-
Inadequate
intake or inadequate exhaust, usually both.
-
Inadequate
heat added to room. Example. Nursery
without maintaining room temperature without heater.
-
Inadequate exhaust openings in natural
buildings.
Nursery
or Finishing: Losses from Strep suis (Ss), Hemophilus parasuis
Hps), or Actinobacillus pleuropneumoniae (App).
Temperature Monitoring
·
Equipment
|
Adequate |
Within 30 F. of Desired Room Temperature (DRT) settings |
Failing |
Room is 30 F. over DRT or 30 F. under DRT. Exception in summer when outside temperature exceeds DRT |
Heating failure. Wrong DRT.
Definition: Different temperatures are found in
different areas of the room at the same time.
Check area with quick-response highly accurate
thermometer. Check front versus back, ceiling versus floor, and corners versus
center.
|
Adequate: |
Temperatures in different parts of a room
area should not differ more than 50 F. (Exception – Tunnel
ventilated buildings, front to back, especially winter.) |
|
Problem: |
Temperature variation of more than 50
F. in the same room. |
Definition: Fluctuating room temperatures related to
different times of the day.
Most common concern is the comparison of room temperature in the late afternoon versus early morning (day at 3 PM versus night at 5 AM).
|
Late Summer - Early Fall |
Room temperatures should not fluctuate more than 150 F. each
day for over 5 days in a row. |
|
All Spring, Most of Summer, Most of Fall, All Winter |
Room temperatures should not fluctuate more than 150 F. a
day. |
Gas pressure: Main line natural gas pressure problems cause falling night time room temperatures in the winter.
Scours in nursery (Rota Virus) and farrowing (Neonatal Diarrhea)
Finishing cough. Finishing pneumonia. Flu in finishing.
Definition: Room temperatures rise and fall every hour
or less
Finding a temperature curve that is fluctuating slowly up and down (more than a 50 F. range) many times a day. Obvious cycling imposed over daily high to low movement. Humidity often cycles with temperature. |
Room sensors are covered, especially if protected in PCV tubes less than 3 inches in diameter. Fans on timers that have too long of a period between cycles. Oversized fans running on timers.
Scours in nursery (Rota Virus). Stressed, tail biting pigs in finisher
during Fall-Winter.
5.
Monitoring Piglet Comfort
Mat Temperatures
|
Mat surface temperatures should be no less than 950 and no more than1000 F. |
Pigs avoiding mats and laying near sow to stay warm.
Higher than normal quantities of healthy pigs being crushed.
Hot Mats: Lamps too close or bulbs too large.
Cool Mats: Lamps too far or bulbs too small. Lamps
placed above the divider.
Hot or Cold: Crushed piglets.
Cold: Pigs are not adequately warmed in
first 24 hours of life. Less likely to nurse well and thrive. Scours if
chilled.
1.
Air
Intake Monitor
Static
Pressure: Digital Manometer, Portable Magnehelic Gauge
Air Speed: Hot-Wire Anemometer, Thermoanemometer, Digital Air Velocity Probe.
Static Pressure:
(Remember to run a tube from the device to the outside.)
|
Target
Room Static Pressure |
.03
inches of water (3 WC) |
Acceptable Static Pressure Range
|
025 to .035 inches of water.
(2.5 to 3.5 WC)
|
Air Speed: Measured at inlets.
|
Air Speed Too Slow |
Less than 700 foot per minute |
|
Acceptable Air Speed |
700 to 1000 foot per minute at inlets |
|
Air Speed Too Fast |
More than 1000 foot per minute |
Static pressure to high: Inadequate intake opening area. Fan louvers may snap shut and open when all fans are turned to maximum. (Choke: Room is “choked” when intake opening is not large enough to supply exhaust fan air demands at maximum output. Static pressure runs over .03 inches and air speed at inlets exceeds 1000 ft/minute.)
Air moving too slow / Static pressure too low: Air mixes inadequately. Temperature stratification occurs. Animals chilled under inlets with piling or diarrhea (piglet or nursery).
Air
moving too fast: Drafts and chilling. Drafts are air movements more
than 30 feet per minute, especially in farrowing crates.
Static Pressure too High/Air Moving too Fast: Inadequate square inches allowed for intake. Restriction may have occurred in pathway of fresh air intake. Need to increase space allowed for intake to maintain set exhaust volume.
Static pressure Normal/Air Moving too Fast: Hallway or other preheating arrangement is heating intake air excessively during cold weather.
Static Pressure too Low/Air
moving too Slow: Reduce the amount of open space for inlet. Reduce “slot width” between
baffle and ceiling. Reset louvers on ceiling or wall inlets. Raise curtain.
Place additional board for curtain to pass in up position in winter for added
“seal” and reset drop. Doors left open when it is cool outside.
Static Pressure High and Choked Inlet Space: Temperature stratification. Diarrhea in parts of the room.
Air
Moving too Slow / Static Pressure too Low: Chill results in piglet
diarrhea near inlet. Nursery finishing pigs refuse to lay under inlet and foul
the sleeping area. Tail biting in winter.
Air
moving too fast: Many farrowing crates with chilled piglets and
diarrhea. Finishing experiences increased rectal prolapses (blowouts). Diarrhea
in young nursery pigs.
2.
Air Exhaust Monitoring
Least Accurate: Hot-Wire Anemometer, Thermoanemometer, Air Velocity Probe
·
Charts
Suggested Exhaust Recommendations: Lists needed CFM for individual animals (or sow and litter) by age and
climate (cool, warm and hot weather). Use table and quantity of pigs to find
the CFM exhaust requirements for room. The cool, warm, and hot recommendations
roughly correspond to stage 1, stage 2, and stage 3. The increase of CFM
capacity over cool, warm, and hot weather relates to the way room fans are
added over increasing temperatures.
Approximate CFM Output of
Exhaust Fans: Table determines the fan output (capacity). Collect
information at the fan to use the table. Measure the fan diameter with a tape
measure. The motor horsepower and motor RPM rating will be on a plate or
sticker on the motor housing.
Tachometer:
|
The RPM rating of fan may be found on a sticker or plate on the fan
housing. Some are not. If fan RPM can not be found, use an anemometer to
check fan efficiency. Do not confuse fan RPM and motor RPM. “Tach” the fan
near center of blades when operating at maximum output. Fans should
deliver the RPM specified. |
Anemometer:
|
Measure with a tape measure the diameter of the fan or the diameter of
round opening around the fan blades. Find the motor horsepower and RPM rating
on motor housing. Use the “Approximate CFM Output of Exhaust Fans” table to find
the CFM output the fan is rated to perform. Measure the fan output when at
maximum speed by placing anemometer sensor in exhaust draft of the fan outside. |
Inadequate Exhaust: High humidity, possible stratification. Most noticeable in the summer.
Excessive Exhaust: Cycling temperatures and
humidity noted on data logger. Chilled pigs. Stressed pigs. Diarrhea.
Pneumonia. Ss/Hps/App.
Fans are inadequate or oversized for exhaust needs.
DRT is set too high and room has no heater.
Fans are not functioning
properly due to worn belts, rusted or broken housings and shrouds, or motor
malfunction.
Heater setting is too close to room DRT.
Excessive Exhaust: The
problems of cycling temperature, especially in winter. Scours in nursery. Stressed, tail biting pigs in
finisher.
Monitoring
Air Distribution
Definition: Air distribution is
monitored to – (1) visualize how air moves in the building, finding small and
large movement patterns. (2) Check airspeed of suspect air movements for rate.
A fast movement (more than 30 ft/minute) is classed as a draft if it affects
critical pig areas where cooling is not needed.
Visualize
Small Air Patterns (One Point in the Room at a Time):
Borozin
Smoke Gun Kit and Refills, Smoke Sticks
Measure Air Speed:
Hot-Wire Anemometer, Thermoanemometer, Air
Velocity Probe
Small Air
Movement Patterns:
|
Trace intake pattern to assure
that fresh air stays high against ceiling and does not fall too soon,
assuring that fresh intake air mixes adequately with room air. Intake air
that falls abruptly into farrowing crates or nursery-finishing sleeping areas
will chill pigs and cause pen fouling or upset pen use habits. |
High Air Speed Drafts:
|
Drafts
moving across pigs, especially sleeping area. Drafts moving into areas
occupied by piglets in farrowing crates. Excessive air movement cased by stir
fans. |
Large Air Movement Patterns:
|
Assure intake evenly
supplies fresh air. Determine how the mass of room air is moving from the
inlets toward exhaust. Patterns should move overhead and down alley ways.
Assure that intake or exhaust air is not leaking into adjoining rooms. Find
air leaks in sidewalls, around fan housings, and doors (unplanned intakes).
Unplanned intakes may be bringing fresh air from outside or stale
contaminated air from another room. |
Chill: Drafts cause diarrhea in piglets. Respiratory disease occurrence in older pigs. Tail biting can be initiated in drafty facilities.
Ammonia Detection Tubes
(with or with out air sampling
pump)
Adequate
|
Less than 15 ppm |
|
|
Caution |
15 to 25 ppm |
|
|
Dangerous |
More than 25 ppm |
|
|
When ammonia is detected as an odor by personally smelling, the level
is greater than 50 ppm. |
||
Ammonia is not a ventilation problem. Buildings are not ventilated to control ammonia levels. Ammonia is a waste management issue. Ammonia only comes from drying urine. As long as urine is contained in water-laden pit, ammonia will not be a problem. Ammonia is highly water-soluble. When ammonia excesses are experienced, check pit levels and look for leaky pit plugs. Old style farrowing house pan-and-auger waste systems are notorious for generating ammonia.
Ammonia is lighter-than-air, but held in the water of the pit effluent. Other pit gases leave the effluent, but are heavier-than-air. Other gases will stay in the pit and “ride” the 18 inches above the effluent like an invisible “head.” Gases are not a problem as long as pit levels are not too high, not too low, and pits are flushed as recommended.
Nasal irritation. More mucus production aids growth of pasteurella bacteria. Pasteurella bacteria cause rhinitis.
Charts
·
Suggested Exhaust
Recommendations (Midwest Planning Service)
|
|
Weight |
Exhaust (CFM per Head) |
||
|
|
Lb. |
Cold <350 |
Warm 350 – 700 |
Hot >700 |
|
Sow and Litter |
400 |
20 cfm |
80 cfm |
500 cfm |
|
Small Nursery Pig |
12-30 |
2 cfm |
10 cfm |
25 cfm |
|
Large Nursery Pig |
30-60 |
3 cfm |
15 cfm |
35 cfm |